LRD3365 Schneider TeSys LRD thermal overload relays - 80...104 A - class 10A
Description
TeSys LRD thermal overload relay, 104A/1000V, thermal setting range 80-104A, tripping class 10A, for protection of 3-phase motors 45kW@400V. Differential device with phase failure and load unbalance detection. It provides a thermal adjustement dial, a manual-automatic reset selector acting also as reset button, a trip test button for simulation of a tripping, a stop button, a flag indicator and 2 auxiliary contacts 1NO+1NC for fault signalling. Settings are protected by a transparent cover lockable by sealing. Connection by screw clamp terminals, it connects directly to the bottom terminals of 3-pole contactors LC1D80-D95. Mounting on DIN rail or screw fixing, separated from the contactor, with use of a terminal block LA7D3064 (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, ATEX, Marine), Green Premium compliant (RoHs/Reach).
Specification
Main
Range
TeSys
Product name
TeSys LRD
TeSys Deca
Product or component type
Differential thermal overload relay
Device short name
LRD
Relay application
Motor protection
Product compatibility
LC1D95
LC1D80
Network type
AC
DC
Thermal overload class
Class 10A conforming to IEC 60947-4-1
Thermal protection adjustment range
80…104 A
[Ui] rated insulation voltage
Power circuit: 1000 V conforming to IEC 60947-4-1
Power circuit: 600 V conforming to CSA
Power circuit: 600 V conforming to UL